HomeMy WebLinkAboutSupplemental - Fire/Life Safety Inspection Report2002 FIRE /LIFE SAFETY INSPECTION REPORT
ADULT /JUVENILE DETENTION FACILITIES
Facility: FACILITY TYPE: (check one)
[ ] Adult max/mad security
N.Adult minimum security
[ ] Juvenile max/med security
[ ] Juvenile minimum security
30- 30 -44- 0034 - 000 -065 -L [ ] Holding Cell(s) only
SEAL BEACH PD
911 SEAL BEACH BLVD
SEAL BEACH CA 90740
An inspection of this facility was conducted per the mandate of Section 13146.1, California Health and Safety
Code, and applicable requirements of Titles 19 and 24, California Code of Regulations. (Check appropriate box)
No deficiencies affecting Fm!!ffa safety were ,noted. Fire cleamno3 is granted.
[ ] Minor deficiencies affecting fire /life safety were noted and are pending correction.
Fire clearance granted
Fire clearance is withheld pending correction of deficiencies. (List of deficiencies is
attached).
[ ] Prisoners are no longer detained at this facility.
The authority conducting the inspection shall submit copies of this report to the appropriate bodies listed
below. Where firellife safety deficiencies are noted, a list of the deficiencies must accompany this report.
• Office of the State Fire Marshal
Building Safety Program
P.O. Box 944246
Sacramento, CA 94244.2460
FAX: (916) 324 -3784
• Board of Corrections
Facilities Standards & Operations Division
600 Bercut Drive
Sacramento, CA 95814
FAX: (916) 3273317
• Official in Charge of the Facility
• Local Governing Body (i.e., Board of Supervisors, City Council, etc.)
Date of Inspection: ri I I�J� DZ �
/� Inspected by: LF1 r`�Ep.�p,t,
Fire Authority: 0Q AN Ut= COV,+6V VIA
Facility Representative:T I /t ✓ IIA� C nr C
0
Go-ise
OMM2
2002 ADULT /JUVENILE DETENTION FACILITY INSPECTION GUIDE
The following is to be used only as a guide and is not intended to include all applicable requirements
A. CONSTRUCTION
Y s No NIA
1.
Building construction type and fire resistive rating conform throughout
[ ] [ ]
and are maintained in good repair. (19 CCR 308.2.2.2; CBC 3.24)
[ 1 [ 1
2.
Proper interior and ceiling finish ratings are provided.
There are no visible defects. (CMC 109.2)
��11
(CBC 308.8.1, Table 3B)
[ ] [ ]
3.
Vertical shaft enclosures are in good repair and fire assemblies at
operated in a safe manner. (19 CCR 3.24)
openings are properly maintained. (CBC 711, Table 6A)
Emergency power is provided for minimal lighting and firellifs safety
B. EXITS
systems. (CBC 1012)
4.
Proper corridor construction and opening protection are provided and
] [ ] [ ]
13.
maintained. Dead -end corridors do not exceed 20 feet in length. (CBC 1005)
[ ] [ ]
5.
All means of egress are unobstructed and free of storage. (19 CCR 3.11)
[ ] [ ]
6.
Exilways and exit signs are illuminated and ,maintained. (CBC 1012, 1013)
[ ] [ ]
7.
Corridors are not used as part of the air distribution system. (CMC 317.9)
[ ] [ ]
8.
Supervisory personnel are continually on duty and effective provisions are
[ ] f ]
made to remove occupants in case of fire or other emergency.
\'
16.
(Penal Code 6030[c])
C. MECHANICALIELECTRICAL
9.
Fire dampers, smoke detectors and similar devices are adequate, properly
ldz4 [ ] [ ]
maintained and tested. (CMC 605; CBC 713.10, 713.11)
10.
All heating, cooling and ventilation equipment is maintained satisfactorily.
There are no visible defects. (CMC 109.2)
��11
11.
Electrical wiring, fixtures and appliances are properly installed and
operated in a safe manner. (19 CCR 3.24)
12.
Emergency power is provided for minimal lighting and firellifs safety
[ ] [ ]
systems. (CBC 1012)
D. HOUSEKEEPING
13.
Kitchen hoods, vents, ducts and filters are adequate, are maintained in
[ ] [ ]
proper condition and are free of grease. (19 CCR 3.19, 3.24)
14.
All areas are free of unacceptable amounts of storage. (19 CCR 3.19)
E. FIRE
EXTINGUISHINGIALARM
15.
All first -aid fire fighting equipment is properly located and maintained.
[ ] [ ]
(19 CCR 3.24, 3.29)
\'
16.
All fire extinguishing systems are properly maintained and serviced.
(19 CCR 3.24)
17.
The automatic fire alarm system is properly maintained. It CCR 3.24)
[ ] [ J
F. TRAININGIPREPLANNING
18.
At least one person is on duty who meets the training standards established
tq?] [ ] [ ]
for general fire and life safety relating specifically to the facility.
(Penal Code 6030[c] and CFC 1303.4.2.1)
inspections by the local fire
{' [ ] [ ]
19.
Fire suppression preplanning are conducted
authority at least every two years. (Penal Code 6031.1)
20.
Fire drills shall be conducted quarterly for each shift. (CFC 1303.3.4.3)
[ ] [ ]
Where any deficiency Is identified, please provide specific information regarding the deficiency type and location (e.g., the
fire alarm in Building C indicated a trouble alarm and must be repaired.)
Rev 0v
2002 FIRE /LIFE SAFETY INSPECTION REPORT
ADULT /JUVENILE DETENTION FACILITIES
Facility: FACILITY TYPE: (check one)
d ]Adult max/med security
uIt minimum security
[ ] Juvenile max/med security
[ ] Juvenile minimum security
30- 30 -44- 0035- 000 -065 -L [] Holding Cells) only
SEAL BEACH JAIL
913 SEAL BEACH BLVD
SEAL BEACH CA 90740
An inspection of this facility was conducted per the mandate of Section 13146.1, California Health and Safety
Code, and applicable requirements of Tides 19 and 24, California Code of Regulations. (Check appropriate box)
4 No deficiencies affecting fire/life safety were noted. Fire clearance is granted.
Minor deficiencies affecting fire/life safety were noted and are pending correction.
Fire clearance granted
Fire clearance is withheld pending correction of deficiencies. (List of deficiencies is
attached).
Prisoners are no longer detained at this facility.
The authority conducting the inspection shall submit copies of this report to the appropriate bodies listed
below. Where finWife safety deficiencies are noted, a list of the deficiencies must accompany this report.
• Office of the State Fire Marshal
Building Safety Program
P.O. Box 944246
Sacramento, CA 94244.2460
FAX: (916) 3243784
• Board of Corrections
Facilities Standards & Operations Division
600 Bercut Drive
Sacramento, CA 95814
FAX: (916) 327.3317
• Official in Charge of the Facility
• Local Governing Body (I.e., Board of Supervisors, City Council, etc.)
Date of Inspection: 4 IS) 02, Inspected by: "
Fire Authority:- eCANGE. C0j i'I14i� Ah T1F 0 14
Facility Representative: SC-IT. !/EFL -ZAtie E,
saia�
maaoz
r
2002 ADULT /JUVENILE DETENTION FACILITY INSPECTION GUIDE
The following is to be used only as a guide and is not intended to include all applicable requirements.
A. CONSTRUCTION Yes No NIA
1. Building construction type and fire resistive rating conform throughout
and are maintained in good repair. (19 CCR 308.2.2.2; CBC 3.24)
2. Proper interior and ceiling finish ratings are provided.
(CBC 308.8.1, Table 3B) /
3. Vertical shaft enclosures are in good repair and fire assemblies at
openings are property maintained. (CBC 711, Table 6A)
B. EXITS
4. Proper corridor construction and opening protection are provided and
maintained. Dead -end corridors do not exceed 20 feet in length. (CBC 1005)
5. Al means of egress are unobstructed and free of storage. (19 CCR 3.11) [ ] [ ]
6. Exitways and exit signs are illuminated and ,maintained. (CBC 1012, 1013) [ ] [ }
7. Corridors are not used as part of the air distribution system. (CMC 317.9) [ ] [ ]
8. Supervisory personnel are continually on duty and effective provisions are
made to remove occupants in case of fire or other emergency.
(Penal Code 60301c])
C. MECHANICAL/ELECTRICAL
9.
Fire dampers, smoke detectors and similar devices are adequate, property
14 [ ] [ ]
maintained and tested. (CMC 605; CBC 713.10, 713.11)
10.
All heating, cooling and ventilation equipment is maintained satisfactorily. [ ]
[ ]
There are no visible defects. (CMC 109.2)
it.
Electrical wiring, fixtures and appliances are property installed and
operated in a safe manner. (19 CCR 3.24)
7�
12.
Emergency power is provided for minimal lighting and firellife safety
systems. (CBC 1012)
D. HOUSEKEEPING
13.
Kitchen hoods, vents, ducts and filters are adequate, are maintained in
[ ] [ ]
proper condition and are free of grease. (19 CCR 3.19, 3.24)
14.
All areas are free of unacceptable amounts of storage. (19 CCR 3.19)
[ ] [ ]
E. FIRE
EXTINGUISHING /ALARM
15.
All first -aid fire fighting equipment Is property located and maintained.
(19 CCR 3.24, 3.29)
16.
All fire extinguishing systems are properly maintained and serviced.
[ ] [ ]
(19 CCR 3.24)
17.
She automatic fire aiami system is property maintained. (19 CCR 3.24)
[ ] [ ]
F. TRAININGIPREPLANNING
18. At least one person is on duty who meets the training standards established Q9 [ ] [ ]
for general fire and life safety relating specifically to the facility.
(Penal Code 6030[c] and CFC 1303.4.2.1) u'
19. Fire suppression preplanning inspections are conducted by the local fire YY [ ] [ ]
authority at least every two years. (Penal Code 6031.1)
20. Fire drills shall be conducted quarterly for each shift. (CFC 1303.3.4.3) [ ] [ ]
Where any deficiency is identified, please provide specific information regarding the deficiency type and location (e.g., the
fire alarm in Building C indicated a trouble alarm and must be repaired.)
Rev 0=W2